  • #16218
    walnut
    Participant

    Visited a Smeg range with the mains cooker switch was burned out.
    The cooker had been connected using 2.5mm twin and earth.
    Smeg’s website rates the Range at 13.1kw.
    Should the mains lead be 6mm or will 4mm do the Job?

    #168880
    A1TEC
    Participant

    Re: Smeg all electric range

    Hi Walnut, would use 6mm cable for any thing above 9kw,rule of thumb says 1.5mm per 3kw.

    Regards

    John.