Earth Loop Testing after repair

Home Forums Trade Technical & Spare Parts Forums Trade Technical Enquiries Earth Loop Testing after repair

Viewing 15 posts - 1 through 15 (of 16 total)
  • Author
    Posts
  • #5440
    woz
    Participant

    Just wondering if any one knows the score on this one

    Is there any regulation where a service engineer has to carry out an Earth Loop Impedance test after carrying out a repair.

    If there is can somebody give me the regulation number as in the IEE regs it only mentions new installations(wiring) not about appliances.

    Regards

    woz 😉

    #111270
    kwatt
    Keymaster

    Hi woz,

    As far as I am aware there is no specific regulation in regard to this for appliance (or much else really) repairs in the home. I think that there was some talk of introducing such a scheme but it was considered too bulky and, basically, unenforceable to be in any way workable.

    Too meet IEE regs or building standards is a different matter altogether but I do know that there is no requirement to loop test a newly installed appliance in a new build.

    You should read the thread about Part P, that explains why it’s unworkable quite well, from memory it’s in the General Trade Forum.

    Hope that helps a little.

    K.

    #111271
    Martin
    Participant

    Re: Earth Loop Testing after repair

    It will only come into play when they change the rules on ‘PAT Testing’ to include repairs to and in private dwellings and to all Whitegoods…..Long way off yet I reckon?

    Meanwhile keep Loop Testing and show on your Invoice/Work Docket the test results as usual…..!

    Martin

    #111272
    woz
    Participant

    Re: Earth Loop Testing after repair

    Thanks Martin

    at the moment our company doesn’t do the loop test.

    Think about it this way 180 X £600 Expensive!!!!!!!

    #111273
    woz
    Participant

    Re: Earth Loop Testing after repair

    Sorry and thanks Ken

    #111274
    woz
    Participant

    Re: Earth Loop Testing after repair

    Hi Ken

    Cannot find the PART P post you mentioned have searched the entire site

    could you shed a little light for me

    Thanks Woz 😆

    #111275
    woz
    Participant

    Re: Earth Loop Testing after repair

    Hi Ken

    Cannot find the PART P post you mentioned have searched the entire site

    could you shed a little light for me

    Thanks Woz 😆

    #111276
    kwatt
    Keymaster
    #111277
    Tinhips
    Participant

    I think HSE require it to be done, but at present can not find the HSE guide, given out and distributed to all DASA members about 18/24 months ago. When I do I will give you the guide number.

    #111278
    Martin
    Participant

    Re: Earth Loop Testing after repair

    The HSE Guide refers only to ‘Electrical Installations’ however DASA included this as part of their ‘Quality Criteria’ Electrical Safety Tests (Section 3.1.7) which all members are expected to adhere on every repair!

    Martin

    #111279
    Scotty
    Participant

    Re: Earth Loop Testing after repair

    The HSE Guide refers only to ‘Electrical Installations’ however DASA included this as part of their ‘Quality Criteria’ Electrical Safety Tests (Section 3.1.7) which all members are expected to adhere on every repair!

    Dasa has recommended since 1993 that earth loop impedence testing should be done.
    It is now part of the dasa Quality criteria, which was done in conjunction and advice from the HSE. I think you will find that the HSE regard this test as compulsary, they explained that to members personaly at the DASA agm (one before last).

    The HSE have an information sheet on safety in domestic appliance servicing:-
    Engineering Information sheet No 35.

    ps
    I will make it available on http://www.dasanet.org.uk, for dasa members to download

    #111280
    kwatt
    Keymaster

    In the “Safety And Electrical Testing At Work” Leaflet it states that:

    Legal requirements
    The Electricity at Work Regulations 1989 are
    the principal legislation relating to electrical
    testing activities. Regulation 4(3) requires that
    ‘work on or near to an electrical system shall be
    carried out in such a manner as not to give rise,
    so far as is reasonably practicable, to danger’.
    Regulation 14 places a strict prohibition on
    working on or near live conductors unless:
    (a) it is unreasonable for the equipment to be
    dead;
    (b) it is reasonable for the work to take place on
    or near the live conductor; and
    (c) suitable precautions have been taken to
    prevent injury.
    In addition, employers are required under
    regulation 3 of the Management of Health
    and Safety at Work Regulations 1999 to
    assess the risks to the health and safety of
    their employees while they are at work, in
    order to identify and implement the
    necessary precautions to ensure safety.

    As is plain, there appears to be no legal requirement, which was the question.

    K.

    #111281
    kwatt
    Keymaster

    Oh the above was taken from the general overview, from the one Scott reffers too the quote would be;

    What are the legal requirements?
    The Electricity at Work Regulations 19893 are the
    principal legislation relating to electrical testing activities
    and regulation 14 is particularly relevant to live testing
    activities. In addition, employers are required under
    regulation 3 of the Management of Health and Safety at
    Work Regulations 19997 to assess the risks to the health
    and safety of their employees while they are at work, in
    order to identify and implement the necessary
    precautions to ensure safety.

    K.

    #111282
    kwatt
    Keymaster

    I just put the PDF in the downloads section, it’s in the PDF documents bit.

    K.

    #111283
    streetlighter
    Participant

    Re: Earth Loop Testing after repair

    personally i feel, on every job I go to I must
    1 test loop impeadance at socket out-let, inc built in polarity test.
    2 earth loop test on appliance, ie multitester from earth on plug to exposed case.
    3 sometimes on old appliances i use remote probe on loop tester to case but must be on rear as somtimes it sparkes and damages case.
    I do this for my own peace of mind and for insurance puposes noting the reading on my and customers sheet.