Please can somebody help i’m tearing me hair out,the compressor runs and the plate gets cold but the water solenoid dosn’t open ,the most voltage it gets between live & neutral is 24volts cant understand why the stats work ok so im stuck be glad of some help if poss cheers Larry 😕 😕
From start up the machine will do an ice making cycle 15 minutes or so even if there is no water in,ie will freeze plate,when ice thickness stat senses its cold enough it engages the hot defrost cyle and supplies the cold water inlet vale which will then fill,you could fill it manually before starting up.Should then cycle normally.
tried all that still wont work when the top stat cuts in still gets 24volts wondering if it could be that small black box at the bottom on the back of the machine not sure what it does
Wiring diagram is on the back or somewhere on the machine usually.
Stick a suction gauge on and check the suction line pressure should be 1 bar ish, if its lower needs leak check weigh in new charge.