sandwhich chiller

Viewing 8 posts - 1 through 8 (of 8 total)
  • Author
    Posts
  • #44272
    andysam
    Participant

    iv just been to a glass fronted sandwhich chiller. it got regassed by someone else. the problem is the compressor is now very noisy. ive checked the refrigerant levels and there ok. is there a chance that it hasnt got enough oil in the compressor? can anyone help.

    #280421
    maltheviking
    Participant

    Re: sandwhich chiller

    andysam wrote:iv just been to a glass fronted sandwhich chiller. it got regassed by someone else. the problem is the compressor is now very noisy. ive checked the refrigerant levels and there ok. is there a chance that it hasnt got enough oil in the compressor? can anyone help.

    Cant see how it’s lost oil, even if it had a gas leak previously,probaly just a noisy or nackered comp. 😯

    #280422
    maltheviking
    Participant

    Re: sandwhich chiller

    andysam wrote:iv just been to a glass fronted sandwhich chiller. it got regassed by someone else. the problem is the compressor is now very noisy. ive checked the refrigerant levels and there ok. is there a chance that it hasnt got enough oil in the compressor? can anyone help.

    Cant see how it’s lost oil, even if it had a gas leak previously,probaly just a noisy or nackered comp. 😯

    #280423
    maltheviking
    Participant

    Re: sandwhich chiller

    Wow a bouble post, long time since I managed that P45 :rolls: :rotl:

    #280424
    Penguin45
    Participant

    Re: sandwhich chiller

    😀

    :p45:

    #280425
    spimps
    Participant

    Re: sandwhich chiller

    What’s
    the compressor no and back pressure.
    Presume it’s on 134a
    Could be non condenseables causing the problem,you can’t be sure of what else (air/moisture etc) went in along with the refrigerant when rechraged sounds like you would have to take out the current refrigerant,pull a fresh vacuum so you know the system is ok and then recharge with refrigerant as marked on the plate.

    #280426
    PINKY
    Participant

    Re: sandwhich chiller

    Assuming they put in the right refrigerant? :rolls:

    #280427
    andysam
    Participant

    Re: sandwhich chiller

    cheers fellas i will try get out all refrigerant and put on a long vac hope it dsnt need a new comp just seen the price for a replacement wot a joke for a bit of metal.