Is this cable suitable for connecting a 4kW double-oven to a 32A supply?

Home Forums Public Support Forums Help And Support Cooker And Oven Forum Is this cable suitable for connecting a 4kW double-oven to a 32A supply?

Viewing 8 posts - 1 through 8 (of 8 total)
  • Author
    Posts
  • #96924
    itm60
    Participant

    I’m looking for electrical cable to connect a double oven to a 32A supply. The oven is rated at 4kW. Can anyone advise on whether this would be suitable?
    https://www.screwfix.com/p/prysmian-6242y-twin-earth-cable-6mm-x-10m-grey/29733
    PRYSMIAN 6242Y TWIN & EARTH CABLE 6MM² X 10M GREY [TABLE]
    [TR]
    SPECIFICATION [/TR]
    [TR]
    [TD]Brand[/TD]
    [TD]Prysmian[/TD]
    [/TR]
    [TR]
    [TD]Cable Code[/TD]
    [TD]6242Y[/TD]
    [/TR]
    [TR]
    [TD]Cable End Type[/TD]
    [TD]Bare[/TD]
    [/TR]
    [TR]
    [TD]Cable Length[/TD]
    [TD]10 m[/TD]
    [/TR]
    [TR]
    [TD]Cable Product Type[/TD]
    [TD]Twin & Earth[/TD]
    [/TR]
    [TR]
    [TD]Cable Profile[/TD]
    [TD]Flat[/TD]
    [/TR]
    [TR]
    [TD]Cable Voltage Rating[/TD]
    [TD]300/500 V[/TD]
    [/TR]
    [TR]
    [TD]CE Standard (Tested to EN…)[/TD]
    [TD]BS 6004.[/TD]
    [/TR]
    [TR]
    [TD]Coil or Drum[/TD]
    [TD]Coil[/TD]
    [/TR]
    [TR]
    [TD]Colour[/TD]
    [TD]Grey[/TD]
    [/TR]
    [TR]
    [TD]Conductor Area[/TD]
    [TD]6 mm²[/TD]
    [/TR]
    [TR]
    [TD]External Diameter[/TD]
    [TD]13.1 mm[/TD]
    [/TR]
    [TR]
    [TD]Indoor/Outdoor Usage[/TD]
    [TD]Indoor[/TD]
    [/TR]
    [TR]
    [TD]Manufacturer Guarantee[/TD]
    [TD]1 Year Guarantee[/TD]
    [/TR]
    [TR]
    [TD]Maximum Operating Temperature[/TD]
    [TD]70 °C[/TD]
    [/TR]
    [TR]
    [TD]Minimum Operating Temperature[/TD]
    [TD]-15 °C[/TD]
    [/TR]
    [TR]
    [TD]Model No[/TD]
    [TD]20147221[/TD]
    [/TR]
    [TR]
    [TD]No. of Cable Cores[/TD]
    [TD]2-Core[/TD]
    [/TR]
    [TR]
    [TD]No. of Strands Per Core[/TD]
    [TD]7 Strands Per Core[/TD]
    [/TR]
    [TR]
    [TD]Pack Size[/TD]
    [TD]1[/TD]
    [/TR]
    [TR]
    [TD]Parent Colour[/TD]
    [TD]Grey[/TD]
    [/TR]
    [TR]
    [TD]Pieces in Pack/Case[/TD]
    [TD]1[/TD]
    [/TR]
    [TR]
    [TD]Product Type[/TD]
    [TD]PVC Flat Wiring Cable[/TD]
    [/TR]
    [TR]
    [TD]Sheath Colour[/TD]
    [TD]Grey[/TD]
    [/TR]
    [TR]
    [TD]Supplier Manufacturer Helpline[/TD]
    [TD]08457 678 345[/TD]
    [/TR]
    [/TABLE]

    It’s longer than I need, but the shortest that I could find in Screwfix!

    #465414
    Specialist01269
    Participant

    Hi: 6mm is more than adequate for what you need.

    #465415
    electrofix
    Moderator

    as above 6mm is more than adequate

    at 4Kw your oven only draws a max of just under 17A so is about 50{e5d1b7155a01ef1f3b9c9968eaba33524ee81600d00d4be2b4d93ac2e58cec2d} of the mcb rating

    If you have a tool station near your screwfix they are slightly cheaper on the cable

    also if you can find a small local electrical wholesaler they can cut cable to length

    Dave

    #465416
    Specialist01269
    Participant

    TLC still do cut to length cable, but not open on Sunday.

    #465417
    itm60
    Participant

    Thanks. Is there any reason that I might use heat resistant cable, which someone has suggested to me?

    #465418
    itm60
    Participant

    …and would 2.5mm cable suffice? Someone has recommended this:
    https://www.screwfix.com/p/nexans-heat-resistant-flex-3183tq-3-core-2-5mm-5m-white/8869t

    #465419
    electrofix
    Moderator

    you can use heat resisting if you want to but its not necessary with an oven. Its more important with a hob where the terminal block is nearer the elements

    Dave

    #465420
    Specialist01269
    Participant

    Heat resistant would be fine and 2.5mm would be ok as it’s rated at 25a, your 4Kw oven should draw a maximum of just under 17a at full power. If using 2.5 flexible then make sure that you get a good wrap around the terminal screw or double it back under the connection clamp and twist the strands together well.